Numerical analyses of the effect of a biphasic thermosyphon vapor channel sizes on the heat transfer intensity when heat removing from a power transformer of combined heat and power station

Результат исследований: Материалы для журналаСтатья

Аннотация

Numerical analyses of the effect of a biphasic thermosyphon vapor channel sizes on the heat transfer intensity was conducted when heat removing from an oil tank of a power transformer of combined heat and power station (CHP). The power transformer cooling system by the closed biphasic thermosyphon was proposed. The mathematical modeling of heat transfer and phase transitions of coolant in the thermosyphon was performed. The problem of heat transfer is formulated in dimensionless variables "velocity vorticity vector - current function - temperature" and solved by finite difference method. As a result of numerical simulation it is found that an increase in the vapor channel length from 0.15m to 1m leads to increasing the temperature difference by 3.5 K.

Язык оригиналаАнглийский
Номер статьи01058
ЖурналMATEC Web of Conferences
Том92
DOI
СостояниеОпубликовано - 21 дек 2016

ASJC Scopus subject areas

  • Chemistry(all)
  • Engineering(all)
  • Materials Science(all)

Fingerprint Подробные сведения о темах исследования «Numerical analyses of the effect of a biphasic thermosyphon vapor channel sizes on the heat transfer intensity when heat removing from a power transformer of combined heat and power station». Вместе они формируют уникальный семантический отпечаток (fingerprint).