Functioning of back-to-back high voltage direct current link model in Tomsk electric power system

A. P. Maltsev, V. E. Rudnik, Y. Yu Malkova, R. A. Ufa

Результат исследований: Материалы для журналарецензирование

Аннотация

In this article the research results of steady-state and dynamic performance of asynchronous back-to-back HVDC link in Tomsk electric power system are presented. It is proposed to use the back-to-back HVDC link to provide an asynchronous link for parallel operation of the North and South parts of Tomsk electric power system. The steady-state stability limit and maximum allowed power flow were defined. Based on this the more effective location and power of back-to-back HVDC link were determined. Therefore, it is shown the application of back-to-back HVDC link decreases the level of short-circuit current, power fluctuations and increases the stability of load operation, especially of motor load at substation.

Язык оригиналаАнглийский
Номер статьи012009
ЖурналIOP Conference Series: Materials Science and Engineering
Том1019
Номер выпуска1
DOI
СостояниеОпубликовано - 20 янв 2021
Событие14th International Forum on Strategic Technology, IFOST 2019 - Tomsk, Российская Федерация
Продолжительность: 14 окт 201917 окт 2019

ASJC Scopus subject areas

  • Materials Science(all)
  • Engineering(all)

Fingerprint Подробные сведения о темах исследования «Functioning of back-to-back high voltage direct current link model in Tomsk electric power system». Вместе они формируют уникальный семантический отпечаток (fingerprint).