Diagnostic of pre-breakdown state of polymeric insulators by the thermovision method

Результат исследований: Материалы для книги/типы отчетовМатериалы для конференции

Аннотация

The possibility of diagnosing the pre-breakdown state of polymeric insulators by the thermovision method is represented in this paper. The diagnostic method is based on the monitoring of time of the appearance of the local temperature difference and the value of the local temperature difference on the insulator surface due to the defect presence inside the insulator volume. Time corresponding to the critical or pre-breakdown state of dielectric may be estimated by means of above mentioned parameters. Good agreement between the experimental results and the model predicted data was found. The deviation between the experimental results and the model predicted time corresponding to the critical (or pre-breakdown) state of dielectric does not exceed 15%.

Язык оригиналаАнглийский
Название основной публикации2007 International Conference on Solid Dielectrics, ICSD
Страницы647-650
Число страниц4
DOI
СостояниеОпубликовано - 2007
Событие2007 International Conference on Solid Dielectrics, ICSD - Winchester, Великобритания
Продолжительность: 8 июл 200713 июл 2007

Другое

Другое2007 International Conference on Solid Dielectrics, ICSD
СтранаВеликобритания
ГородWinchester
Период8.7.0713.7.07

ASJC Scopus subject areas

  • Electrical and Electronic Engineering

Fingerprint Подробные сведения о темах исследования «Diagnostic of pre-breakdown state of polymeric insulators by the thermovision method». Вместе они формируют уникальный семантический отпечаток (fingerprint).