Special field measurement results of an onshore wind farm connected to power grid of Taiwan Power System subject to Typhoon Matmo

Li Wang, Shun Chin Ke, Ting Wei Hong, Chien Hsiang Yu, Chuan Chieh Yeh, Wei Sheng Liu, Bing Lin Kuan, Xiu Yu Lu, Anton V. Prokhorov

Research output: Chapter in Book/Report/Conference proceedingConference contribution

1 Citation (Scopus)

Abstract

This paper studies and analyzes the special power-quality measurement results of a commercial onshore wind farm connected to the power grid of Taiwan Power System when Typhoon Matmo passed through Taiwan. This Kuan-Yuan onshore wind farm of 28.5 MW with nineteen 1.5-MW wind-turbine generator (WTGs) based on doubly-fed induction generator (DFIG) is connected to Kuan-Yin primary substation through two of four step-up main transformers of 161/69 kV, 200 MVA. The measured data were recorded from July 22, 2014 to July 29, 2014 for total 7 days. During the measurement period, Typhoon Matmo just passed through Taiwan and the nineteen WTGs were forced to stop. Special operating characteristics of the studied Kuan-Yuan wind farm subject to Typhoon Matmo were also recorded and studied. According to the measured results, the power quality of the studied Kuan-Yuan onshore wind farm during the measurement period can meet the grid code of Taiwan Power Company (TPC) except the voltage flicker of ΔV10. The time and date of the measured reactive power, maximum voltage variation, maximum voltage flicker, and maximum total demand distortion of current of the studied onshore wind farm related to the time and date of Typhoon Matmo are also discussed.

Original languageEnglish
Title of host publication2017 IEEE/IAS 53rd Industrial and Commercial Power Systems Technical Conference, I and CPS 2017
PublisherInstitute of Electrical and Electronics Engineers Inc.
ISBN (Electronic)9781509057245
DOIs
Publication statusPublished - 8 Jun 2017
Event53rd IEEE/IAS Industrial and Commercial Power Systems Technical Conference, I and CPS 2017 - Niagara Falls, Canada
Duration: 6 May 201711 May 2017

Conference

Conference53rd IEEE/IAS Industrial and Commercial Power Systems Technical Conference, I and CPS 2017
CountryCanada
CityNiagara Falls
Period6.5.1711.5.17

Fingerprint

Onshore wind farms
Turbogenerators
Power quality
Wind turbines
Electric potential
Asynchronous generators
Reactive power
Industry

Keywords

  • doubly-fed induction generators
  • field measurements
  • grid code
  • harmonics
  • onshore wind farm
  • Power quality
  • typhoon
  • voltage flickers
  • voltage variations

ASJC Scopus subject areas

  • Energy Engineering and Power Technology
  • Electrical and Electronic Engineering

Cite this

Wang, L., Ke, S. C., Hong, T. W., Yu, C. H., Yeh, C. C., Liu, W. S., ... Prokhorov, A. V. (2017). Special field measurement results of an onshore wind farm connected to power grid of Taiwan Power System subject to Typhoon Matmo. In 2017 IEEE/IAS 53rd Industrial and Commercial Power Systems Technical Conference, I and CPS 2017 [7945115] Institute of Electrical and Electronics Engineers Inc.. https://doi.org/10.1109/ICPS.2017.7945115

Special field measurement results of an onshore wind farm connected to power grid of Taiwan Power System subject to Typhoon Matmo. / Wang, Li; Ke, Shun Chin; Hong, Ting Wei; Yu, Chien Hsiang; Yeh, Chuan Chieh; Liu, Wei Sheng; Kuan, Bing Lin; Lu, Xiu Yu; Prokhorov, Anton V.

2017 IEEE/IAS 53rd Industrial and Commercial Power Systems Technical Conference, I and CPS 2017. Institute of Electrical and Electronics Engineers Inc., 2017. 7945115.

Research output: Chapter in Book/Report/Conference proceedingConference contribution

Wang, L, Ke, SC, Hong, TW, Yu, CH, Yeh, CC, Liu, WS, Kuan, BL, Lu, XY & Prokhorov, AV 2017, Special field measurement results of an onshore wind farm connected to power grid of Taiwan Power System subject to Typhoon Matmo. in 2017 IEEE/IAS 53rd Industrial and Commercial Power Systems Technical Conference, I and CPS 2017., 7945115, Institute of Electrical and Electronics Engineers Inc., 53rd IEEE/IAS Industrial and Commercial Power Systems Technical Conference, I and CPS 2017, Niagara Falls, Canada, 6.5.17. https://doi.org/10.1109/ICPS.2017.7945115
Wang L, Ke SC, Hong TW, Yu CH, Yeh CC, Liu WS et al. Special field measurement results of an onshore wind farm connected to power grid of Taiwan Power System subject to Typhoon Matmo. In 2017 IEEE/IAS 53rd Industrial and Commercial Power Systems Technical Conference, I and CPS 2017. Institute of Electrical and Electronics Engineers Inc. 2017. 7945115 https://doi.org/10.1109/ICPS.2017.7945115
Wang, Li ; Ke, Shun Chin ; Hong, Ting Wei ; Yu, Chien Hsiang ; Yeh, Chuan Chieh ; Liu, Wei Sheng ; Kuan, Bing Lin ; Lu, Xiu Yu ; Prokhorov, Anton V. / Special field measurement results of an onshore wind farm connected to power grid of Taiwan Power System subject to Typhoon Matmo. 2017 IEEE/IAS 53rd Industrial and Commercial Power Systems Technical Conference, I and CPS 2017. Institute of Electrical and Electronics Engineers Inc., 2017.
@inproceedings{29f438bbe7b143b897188d2ec5a2ffe9,
title = "Special field measurement results of an onshore wind farm connected to power grid of Taiwan Power System subject to Typhoon Matmo",
abstract = "This paper studies and analyzes the special power-quality measurement results of a commercial onshore wind farm connected to the power grid of Taiwan Power System when Typhoon Matmo passed through Taiwan. This Kuan-Yuan onshore wind farm of 28.5 MW with nineteen 1.5-MW wind-turbine generator (WTGs) based on doubly-fed induction generator (DFIG) is connected to Kuan-Yin primary substation through two of four step-up main transformers of 161/69 kV, 200 MVA. The measured data were recorded from July 22, 2014 to July 29, 2014 for total 7 days. During the measurement period, Typhoon Matmo just passed through Taiwan and the nineteen WTGs were forced to stop. Special operating characteristics of the studied Kuan-Yuan wind farm subject to Typhoon Matmo were also recorded and studied. According to the measured results, the power quality of the studied Kuan-Yuan onshore wind farm during the measurement period can meet the grid code of Taiwan Power Company (TPC) except the voltage flicker of ΔV10. The time and date of the measured reactive power, maximum voltage variation, maximum voltage flicker, and maximum total demand distortion of current of the studied onshore wind farm related to the time and date of Typhoon Matmo are also discussed.",
keywords = "doubly-fed induction generators, field measurements, grid code, harmonics, onshore wind farm, Power quality, typhoon, voltage flickers, voltage variations",
author = "Li Wang and Ke, {Shun Chin} and Hong, {Ting Wei} and Yu, {Chien Hsiang} and Yeh, {Chuan Chieh} and Liu, {Wei Sheng} and Kuan, {Bing Lin} and Lu, {Xiu Yu} and Prokhorov, {Anton V.}",
year = "2017",
month = "6",
day = "8",
doi = "10.1109/ICPS.2017.7945115",
language = "English",
booktitle = "2017 IEEE/IAS 53rd Industrial and Commercial Power Systems Technical Conference, I and CPS 2017",
publisher = "Institute of Electrical and Electronics Engineers Inc.",
address = "United States",

}

TY - GEN

T1 - Special field measurement results of an onshore wind farm connected to power grid of Taiwan Power System subject to Typhoon Matmo

AU - Wang, Li

AU - Ke, Shun Chin

AU - Hong, Ting Wei

AU - Yu, Chien Hsiang

AU - Yeh, Chuan Chieh

AU - Liu, Wei Sheng

AU - Kuan, Bing Lin

AU - Lu, Xiu Yu

AU - Prokhorov, Anton V.

PY - 2017/6/8

Y1 - 2017/6/8

N2 - This paper studies and analyzes the special power-quality measurement results of a commercial onshore wind farm connected to the power grid of Taiwan Power System when Typhoon Matmo passed through Taiwan. This Kuan-Yuan onshore wind farm of 28.5 MW with nineteen 1.5-MW wind-turbine generator (WTGs) based on doubly-fed induction generator (DFIG) is connected to Kuan-Yin primary substation through two of four step-up main transformers of 161/69 kV, 200 MVA. The measured data were recorded from July 22, 2014 to July 29, 2014 for total 7 days. During the measurement period, Typhoon Matmo just passed through Taiwan and the nineteen WTGs were forced to stop. Special operating characteristics of the studied Kuan-Yuan wind farm subject to Typhoon Matmo were also recorded and studied. According to the measured results, the power quality of the studied Kuan-Yuan onshore wind farm during the measurement period can meet the grid code of Taiwan Power Company (TPC) except the voltage flicker of ΔV10. The time and date of the measured reactive power, maximum voltage variation, maximum voltage flicker, and maximum total demand distortion of current of the studied onshore wind farm related to the time and date of Typhoon Matmo are also discussed.

AB - This paper studies and analyzes the special power-quality measurement results of a commercial onshore wind farm connected to the power grid of Taiwan Power System when Typhoon Matmo passed through Taiwan. This Kuan-Yuan onshore wind farm of 28.5 MW with nineteen 1.5-MW wind-turbine generator (WTGs) based on doubly-fed induction generator (DFIG) is connected to Kuan-Yin primary substation through two of four step-up main transformers of 161/69 kV, 200 MVA. The measured data were recorded from July 22, 2014 to July 29, 2014 for total 7 days. During the measurement period, Typhoon Matmo just passed through Taiwan and the nineteen WTGs were forced to stop. Special operating characteristics of the studied Kuan-Yuan wind farm subject to Typhoon Matmo were also recorded and studied. According to the measured results, the power quality of the studied Kuan-Yuan onshore wind farm during the measurement period can meet the grid code of Taiwan Power Company (TPC) except the voltage flicker of ΔV10. The time and date of the measured reactive power, maximum voltage variation, maximum voltage flicker, and maximum total demand distortion of current of the studied onshore wind farm related to the time and date of Typhoon Matmo are also discussed.

KW - doubly-fed induction generators

KW - field measurements

KW - grid code

KW - harmonics

KW - onshore wind farm

KW - Power quality

KW - typhoon

KW - voltage flickers

KW - voltage variations

UR - http://www.scopus.com/inward/record.url?scp=85021984420&partnerID=8YFLogxK

UR - http://www.scopus.com/inward/citedby.url?scp=85021984420&partnerID=8YFLogxK

U2 - 10.1109/ICPS.2017.7945115

DO - 10.1109/ICPS.2017.7945115

M3 - Conference contribution

BT - 2017 IEEE/IAS 53rd Industrial and Commercial Power Systems Technical Conference, I and CPS 2017

PB - Institute of Electrical and Electronics Engineers Inc.

ER -