Protection of complete switchgear against arc faults based on comparison of filter unbalance current [Zabezpieczenie rozdzielnic elektrycznych przed wyładowaniami łukowymi bazujaogonekce na porównaniu praogonekdu niezrównoważenia filtru]

Translated title of the contribution: Protection of complete switchgear against arc faults based on comparison of filter unbalance current

Mark Kletsel, Bauyrzhan Mashrapov

Research output: Contribution to journalArticle

Abstract

The paper introduces protection of complete switchgear cells against arc faults which controls the ratio of the unbalanced currents of zerosequence current filter and zero-sequence current transformer. The examples of its implementation on a semiconductor elements and software are given. The analysis of work in different modes and the methods for selecting settings and evaluating the sensitivity are proposed.

Original languageUndefined/Unknown
Pages (from-to)204-206
Number of pages3
JournalPrzeglad Elektrotechniczny
Volume90
Issue number5
DOIs
Publication statusPublished - 2014